Products
Quick Links
About US
Support
Cooperative partner
Copyright © 2022 Fonrich (Shanghai) New Energy Technology Co., Ltd. All rights reserved. 沪ICP备18039308号-1
(1) The Main Controller Module has a black screen. When the multimeter measures a DC voltage between PV + and PV-> 400v, the Main Control Module needs to be replaced.
(2) The data of the combiner box cannot be viewed in the background, and the settings (baud rate, parity, address) of the monitoring module are correct.
(3) Remove the RS485 communication cable of the AB terminal of the controller module and measure the DC voltage between the AB terminals is less than 2v, you need to replace the Main Control Module